160 GPM (606 L/min) at a maximum operating pressure of up to 300 PSI (20.7 BAR)
300 GPM (1135.6 L/min) at a maximum operating pressure of up to 300 PSI (20.7 BAR)
500 GPM (1893 L/min) at a maximum operating pressure of up to 300 PSI (20.7 BAR)
ULTRAFLOW SYSTEM COMPONENTS:
- One (1) Tellurus Touchscreen HMI – 8″ or 15″
- One (1) Primary System Control Module
- One (1) Hydraulic Pump
- One (1) Hydraulic Motor
- One (1) Hydraulic Oil Cooler with Temperature Controller
- One (1) Hydraulic Reservoir with Filtering System
- One (1) 160 GPM, 300 GPM or 500 GPM @ 300 PSI (606, 1135.6 or 1893 L/min @ 20.7 BAR) Concentrate Pump
- One (1) Concentrate Pump Discharge Pressure Transducer
- Discharge Control Nodes (one per solution capable discharge outlet)
- Magnetic Flowmeters (one per solution capable discharge outlet)
- Ratio Control Valves (one per solution capable discharge outlet)
- Check Valves (one per Ratio Control Valves)
- Paddlewheel Flowmeters, solution capable outlet waterway (one per discharge, sized for discharge flow capability)
- Primary Control and Power Cables, one set (1) each
- Ratio Control and Power Cables (one set per solution capable discharge outlet)
OEM SUPPLIED COMPONENTS:
- Hydraulic Hoses and Couplings
- Hydraulic Pressure Gauge
- Hydraulic Temperature Gauge
- Concentrate Hoses and Piping
LOW-FLOW OPTION: The Low-Flow option allows the ULTRAFLOW system to operate below the lowest available capacity of the Concentrate Pump by by-passing excess differential flow back to the pump inlet. When enabled, this feature is handled automatically by the Primary System Control Module with the inclusion of the following additional components:
- One (1) Low-Flow Control Node
- One (1) Magnetic Flowmeter
- One (1) Ratio Control Valve
- One (1) CAN Bus Cable
- One (1) Magnetic Flowmeter Cable
- One (1) Power Cable to Ratio Control Valve
MANUAL OVERRIDE OPTION: The Manual Override option provides a mechanism for by-passing the ULTRAFLOW control system to operate the Concentrate Pump in a fixed concentrate pressure or proportional water pressure. When override is active, Ratio Control Valves will be unpowered and can be manually operated to adjust concentrate injection into selected discharges. Manual Override Option includes the following additional components:
- One (1) Manual Override Panel Switch
- One (1) Override Logic Controller
- One (1) Override Power Relay
- One (1) Water Pump Discharge Pressure Transducer
- One (1) Associated Power and Control Cables